Weil McLain Boiler CGt SERIES User Manual

CGt SERIES BOILER  
SUGGESTED SPECIFICATIONS  
I. General Requirements  
A. Furnish and install ( ) low pressure packaged cast iron sectional boiler(s) that  
operate under induced draft.  
B. Install boiler-burner unit(s) in compliance with manufacturers installation instructions.  
All work must be done in a neat and workman like manner.  
C. Weil-McLain qty.( ) CGt ( ) PIN boiler(s) capable of burning natural gas at 5 to  
13”w.c.  
1. Packaged boiler (standard).  
2. Natural or propane gas fired.  
3. Water.  
4. Minimum 82% efficiency.  
5. Induced draft.  
6. Built-in Tankless Domestic Water Heater  
D. Boiler(s) shall have I=B=R Hydronics Institute gross output(s) at 100% firing rate –  
108 MBH per boiler.  
E. Boiler(s) shall be manufactured by ISO 9001 registered company to conform to  
Section IV of  
the ASME Boiler and Pressure Vessel Code.  
1. Individual sections (and section assembly) to be hydrostatically pressure tested  
at factory in accordance with ASME requirements.  
2. Maximum allowable working pressure 50 PSIG water and cast as part of  
section with ASME symbol.  
F. Regulatory Requirements  
1. Boiler(s) and controls to comply with applicable regulations.  
G. Submittals  
1. Submit shop drawings and product data.  
2. Submittal packet to include boiler (and burner) manufacturer descriptive  
literature, installation instructions, operating instructions, and maintenance  
instructions.  
II.  
Product  
1
 
a) Water boiler(s) controls furnished:  
1) High temperature limit setting to be 140 – 240 degrees.  
2) Combination pressure-temperature gauge with dial clearly marked  
and easy to read, installed with well for removal without draining the  
boiler.  
3) ASME certified pressure relief valve, set to relieve at 30 PSIG.  
Optional relief valves available up to and including maximum  
allowable pressure. Side outlet discharge type; contractor to pipe  
outlet to floor drain or near floor, avoiding any area where freezing  
could occur.  
4) Integrated spark module for blower control with indicator lights for  
easy troubleshooting.  
E. Boiler Manuals:  
1. Boiler, gas control and user’s information manual.  
2. Venting supplements and instructions.  
Weil-McLain  
500 Blaine Street  
Michigan City, IN 46360-2388  
3
C-879 (0700)  
 

Weslo Treadmill WCTL28090 User Manual
Weslo Treadmill WCTL38410 User Manual
Whirlpool Dehumidifier DH25G0 User Manual
Whirlpool Washer Dryer W10343071A User Manual
Woodstock Staple Gun W1779 User Manual
Xantech Universal Remote 48095D User Manual
Zanussi Cooktop ZKF 661 LN User Manual
Zanussi Freezer DV67 User Manual
Zanussi Range 200102 User Manual
Zenoah Chainsaw G415AVS User Manual