Wolf Appliance Company Ventilation Hood 811504 User Manual

INSTALLATION GUIDE  
Pro Wall Ventilation Hoods  
 
Wolf Pro Wall Ventilation Hoods  
Pro Wall Hood Installation  
3
wolfappliance.com/specs  
IMPORTANT NOTE: This installation must be completed  
by a qualified installer or Wolf authorized service center  
technician.  
Wolf Pro Wall Hood  
Model Number  
Serial Number  
Read this entire installation guide prior to installation and  
save for the local inspector’s reference. The homeowner  
should keep this installation guide for future reference.  
This appliance must be installed in accordance with  
National Electrical Codes, as well as all state, municipal  
and local codes. The correct voltage, frequency and  
amperage must be supplied to the appliance from a dedi-  
cated, grounded circuit which is protected by a properly  
sized circuit breaker or time delay fuse. The proper  
voltage, frequency, and amperage ratings are listed on the  
product rating plate.  
Record the model and serial numbers before installing the  
ventilation hood. Both numbers are listed on the product  
rating plate, located inside the left wall of the hood shell.  
Refer to the illustration below.  
RATING PLATE (INSIDE HOOD)  
Location of rating plate.  
 
Installation Considerations  
4
Installation Considerations  
IMPORTANT INSTRUCTIONS  
Pro wall hoods are recommended for use with all Wolf  
TO REDUCE THE RISK OF FIRE, ELECTRIC  
SHOCK OR INJURY, OBSERVE THE FOLLOWING:  
cooking appliances and should be at least as wide as the  
cooking surface. The ventilation hood be installed 30"  
(762) to 36" (914) above the countertop.  
Installation work and electrical wiring must be  
done by qualified person(s) in accordance with all  
applicable codes and standards, including fire-rated  
construction.  
IMPORTANT NOTE: For optimal performance in wall hood  
applications, a pro 27" (686) deep wall hood is recom-  
mended for use with ranges and rangetops that contain a  
charbroiler or griddle.  
Two installers are recommended due to the size and  
weight of the pro ventilation hood.  
BLOWER ASSEMBLIES  
Install the pro ventilation hood only with a blower  
manufactured by Wolf.  
Pro ventilation hoods are shipped without the blower  
assembly. Internal, in-line and remote blowers are avail-  
able through your authorized Wolf dealer. For local dealer  
information, visit the find a showroom section of our  
website, wolfappliance.com.  
When cutting or drilling into wall or ceiling, do not  
damage electrical wiring and other hidden utilities.  
Ducted fans must always be vented to the outdoors.  
The blower will vary in size and is dictated by the cooking  
surface, the volume of air that needs to be moved and the  
length of the duct run. Refer to ventilation recommenda-  
tions in the Wolf design guide.  
To reduce the risk of fire and properly exhaust air,  
be certain to duct air outside. Do not vent exhaust  
air into spaces within walls or ceilings or into attics,  
crawl spaces or garages.  
IMPORTANT NOTE: Use only a Wolf blower with the pro  
ventilation hood.  
 
Pro Wall Hood Specifications  
5
wolfappliance.com/specs  
Overall Dimensions  
LOW-PROFILE WALL HOODS  
12"  
(305)  
10" (254)  
OVERALL  
HEIGHT  
4" (102)  
22" (559)  
OVERALL DEPTH  
30" (762), 36" (914), 42" (1067)  
AND 48" (1219) WIDTHS  
24" (610) DEEP WALL HOODS  
12"  
(305)  
18" (457)  
OVERALL  
HEIGHT  
4" (102)  
24" (610)  
OVERALL DEPTH  
30" (762), 36" (914), 42" (1067), 48" (1219)  
54" (1372), 60" (1524) AND 66" (1676) WIDTHS  
27" (686) DEEP WALL HOODS  
12"  
(305)  
18" (457)  
OVERALL  
HEIGHT  
4" (102)  
27" (686)  
OVERALL DEPTH  
30" (762), 36" (914), 42" (1067), 48" (1219)  
54" (1372), 60" (1524) AND 66" (1676) WIDTHS  
 
Pro Wall Hood Specifications  
6
Installation Specifications  
LOW-PROFILE WALL HOODS  
6"  
LOCATION OF ELECTRICAL  
E
(152)  
5"  
10" (254)  
HEIGHT  
(127)  
OF HOOD  
WIDTH OF HOOD  
30" (762) TO 36" (914)  
TO COUNTERTOP  
22" (559)  
DEPTH OF HOOD  
24" AND 27" DEEP WALL HOODS  
6"  
LOCATION OF ELECTRICAL  
E
(152)  
5"  
(127)  
18" (457)  
HEIGHT  
OF HOOD  
WIDTH OF HOOD  
30" (762) TO 36" (914)  
TO COUNTERTOP  
24" (610) OR  
27" (686)  
DEPTH OF HOOD  
 
Pro Wall Hood Specifications  
Electrical Requirements  
7
wolfappliance.com/specs  
Installation Options  
Wolf pro ventilation hoods require a separate, grounded  
120 V AC, 60 Hz power supply. The service should have its  
own 15 amp circuit breaker. Locate the electrical supply  
flush with back wall and within the shaded area shown in  
the illustration for your specific model on the previous  
page.  
HORIZONTAL DISCHARGE  
Pro low-profile wall hoods have an adjustable discharge.  
Pro 24" (610) and 27" (686) deep wall hoods have a  
vertical discharge. A horizontal discharge kit is available  
through your authorized Wolf dealer. For local dealer infor-  
mation, visit the find a showroom section of our website,  
wolfappliance.com.  
IMPORTANT NOTE: You must follow all National Electrical  
Code regulations. In addition, be aware of local codes and  
ordinances when installing your service.  
RECIRCULATING INSTALLATION  
Pro wall hoods, 30" (762) and 36" (914) wide, with an  
internal blower (600 CFM or less), can be used in a non-  
ducted application with a recirculating filter. In this installa-  
tion, kitchen air is purified through filters and returned as  
clean air into the room. A recirculation kit available through  
your authorized Wolf dealer is required. For local dealer  
information, visit the find a showroom section of our  
website, wolfappliance.com.  
Electrical service for the ventilation hood must be  
installed by a qualified electrician in accordance with  
all applicable national and local electrical codes.  
DUCT COVER  
Optional stainless steel duct covers are available in a  
variety of heights for all pro ventilation hoods through  
your authorized Wolf dealer. For local dealer information,  
visit the find a showroom section of our website,  
wolfappliance.com.  
BACKSPLASH  
Optional stainless steel backsplashes are available in  
widths to match all pro wall hoods through your authorized  
Wolf dealer. For local dealer information, visit the find a  
showroom section of our website, wolfappliance.com.  
 
Pro Wall Hood Specifications  
8
Discharge Specifications  
LOW-PROFILE WALL HOODS  
LOW-PROFILE WALL HOODS DISCHARGE OPTIONS  
The illustrations provide dimensions for discharge options  
for low-profile wall hoods. These dimensions are critical  
for proper installation. Dimension A in the illustrations will  
vary with the width of the hood. Refer to the chart below.  
5
2 /8" (60)  
1
1 /2" (38)  
TO CENTER  
OF TRANSITION  
IMPORTANT NOTE: The transition included with the 500  
CFM internal blower accommodates 31/4" (83) x 10" (254)  
ductwork. An optional 31/4" (83) x 10" (254) to 8" (203)  
round transition is available through your authorized Wolf  
dealer. For local dealer information, visit the find a  
showroom section of our website, wolfappliance.com.  
A
TO  
CENTER OF  
TRANSITION  
Vertical discharge.  
Low-Profile Wall Hoods  
WIDTH OF HOOD  
30" (762)  
36" (914)  
42" (1067)*  
48" (1219)*  
A
143/4" (375)  
173/4" (451)  
203/4" (527)  
233/4" (603)  
1
1 /2" (38)  
*500 CFM blower not available for these hood widths.  
2" (51)  
TO CENTER  
OF TRANSITION  
A
TO  
DISCHARGE  
CUT-OUT  
14"  
CENTER OF  
TRANSITION  
(356)  
Horizontal discharge.  
1
3 /4"  
(83)  
9"  
(229)  
5
5 /8" (143)  
TO CENTER  
OF TRANSITION  
Cut-out without transition.  
A
TO  
CENTER OF  
TRANSITION  
Vertical discharge with accessory transition.  
 
Pro Wall Hood Specifications  
9
wolfappliance.com/specs  
Discharge Specifications  
Duct Cover  
24" AND 27" DEEP WALL HOODS  
IMPORTANT NOTE: If an optional duct cover is to be used  
with any pro wall hood, it must be attached before  
installing the hood. Installing a duct cover will impact all  
aspects of the hood installation including hood location,  
ducting, electrical placement and the mounting surface.  
The illustration below provides dimensions for vertical  
discharge for 24" (610) and 27" (686) deep wall hoods.  
These dimensions are critical for proper installation.  
Dimension A in the illustration will vary with the width of  
the hood. Refer to the chart below.  
DUCT COVER INSTALLATION  
An optional horizontal discharge kit is available through  
your authorized Wolf dealer. For local dealer information,  
visit the find a showroom section of our website,  
wolfappliance.com.  
Remove all screws from the front edge of the back  
panel on the top of the wall hood. Leave the two  
screws on the sides, there is a relief in the duct cover  
for them.  
Attach the duct cover from the inside of the hood  
through the filter opening using the screws provided.  
24" and 27" Deep Wall Hoods  
WIDTH OF HOOD  
30" (762)  
36" (914)  
42" (1067)*  
48" (1219)*  
54" (1372)*  
60" (1524)*  
66" (1676)*  
A
143/4" (375)  
173/4" (451)  
203/4" (527)  
233/4" (603)  
263/4" (679)  
293/4" (756)  
323/4" (832)  
Leave screws partially loose until all screws are  
installed. Check alignment of the duct cover with the  
hood and tighten the four corner screws to secure the  
duct cover. Tighten all remaining screws.  
Proceed with installation of the wall hood.  
DUCT COVER  
9"  
(229)  
5
5 /8" (143)  
TO CENTER  
OF TRANSITION  
MOUNTING  
SCREWS  
A
TO  
CENTER OF  
TRANSITION  
Duct cover installation.  
24" and 27" deep wall hoods—vertical discharge.  
 
Pro Wall Hood Installation  
10  
Install Ductwork  
Pro 24" (610) and 27" (686) deep wall hoods have a  
vertical discharge. If a horizontal discharge is necessary,  
an accessory horizontal discharge kit is required. Refer to  
installation instructions provided with the kit. Accessory  
kits are available through your authorized Wolf dealer. For  
local dealer information, visit the find a showroom section  
of our website, wolfappliance.com.  
To reduce the risk of fire, use only metal ductwork.  
IMPORTANT NOTE: Pro ventilation hoods must exhaust to  
the outdoors except when used with the accessory recir-  
culating kit (30" and 36" wide hoods only).  
Always install a roof or wall cap if you are not installing a  
remote blower. Connect 10" (254) round metal ductwork to  
the cap and work back towards the hood. Use duct tape  
to seal joints between ductwork sections.  
Wolf recommends that the pro wall hood be installed  
30" (762) to 36" (914) above the countertop. Consult a  
qualified HVAC engineer for specific ducting applications.  
A 10" (254) round duct is recommended for pro ventilation  
hoods. Use only metal ductwork, do not use flex ducting.  
Pro 24" (610) and 27" (686) deep wall hoods have a back-  
draft damper included in the transition assembly. Local  
codes may require the use of an additional backdraft  
damper. Contact your local HVAC professional for specific  
requirements. In cold weather installations, a backdraft  
damper is necessary to minimize the backflow of cold air  
into the room.  
Decide where the ductwork will run between the wall hood  
and the outside. A straight, short duct run will allow the  
hood to perform most efficiently. Limit the number of  
elbows and transitions. The duct run should be no longer  
than 50' (15 m). There is a possibility of noise issues, if a  
remote blower is used with a short duct run.  
Local building codes may require the use of make-up air.  
Consult your local HVAC professional for specific require-  
ments in your area.  
Pro low-profile wall hoods allow for a horizontal or vertical  
discharge. When using an in-line or external blower, an  
optional 10" (254) round transition is available through  
your authorized Wolf dealer. For local dealer information,  
visit the find a showroom section of our website,  
wolfappliance.com.  
IMPORTANT NOTE: The transition included with the 500  
CFM internal blower accommodates 31/4" (83) x 10" (254)  
ductwork. An optional 31/4" (83) x 10" (254) to 8" (203)  
round transition is available through your authorized Wolf  
dealer.  
 
Pro Wall Hood Installation  
11  
wolfappliance.com/specs  
Install Ductwork  
LOW-PROFILE WALL HOODS  
24" AND 27" DEEP WALL HOODS  
DUCTWORK INSTALLATION  
THROUGH ROOF  
DUCTWORK INSTALLATION  
THROUGH ROOF  
18" (457)  
HEIGHT OF HOOD  
10" (254)  
HEIGHT OF HOOD  
22" (559)  
DEPTH OF HOOD  
24" (610) OR  
27" (686)  
DEPTH OF HOOD  
30" (762) TO 36" (914)  
COUNTERTOP  
TO BOTTOM OF  
HOOD  
30" (762) TO 36" (914)  
COUNTERTOP  
TO BOTTOM OF  
HOOD  
NOTE: 10" (254) ROUND TRANSITION SHOWN IN VERTICAL DISCHARGE APPLICATION  
WITH IN-LINE OR REMOTE BLOWER. REFER TO INSTALLATION INSTRUCTIONS FOR  
HORIZONTAL DISHCARGE.  
NOTE: HORIZONTAL DISCHARGE REQUIRES AN ACCESSORY KIT.  
 
Pro Wall Hood Installation  
12  
Low-Profile Wall Hoods  
WALL PREPARATION  
HOOD PREPARATION  
Construct the wall framing as shown in the illustration  
below. Be sure to locate horizontal framing using the  
desired installation height of the hood. Refer to the  
illustration below for the location of mounting holes for  
low-profile wall hoods.  
IMPORTANT NOTE: For low-profile wall hoods using the  
500 CFM internal blower, refer to installation instructions  
provided with the blower assembly. Install the internal  
blower prior to mounting the hood.  
If a duct cover is to be used, follow the instructions on  
page 9 before installing the hood. If you are installing a  
recirculating kit, refer to instructions included with the kit  
before installing the hood.  
Framing must be tied together and to ceiling joists to  
provide enough structural strength to support the  
weight of the hood and internal blower, if applicable.  
Remove the filters by pushing each filter up at the  
angle it is placed in, and rotate down. Refer to the  
illustration below. Remove the center filter first. Gloves  
should be worn when handling filters.  
If you are using an in-line or remote blower, attach the  
optional 10" (254) round transition or custom piece to  
the top of the wall hood using holes provided.  
WIDTH OF HOOD  
1
26 /4" (667) TO  
FRAMING STUD CENTERS  
If you are installing an in-line or remote blower, drill a  
7/8" (22) hole through the wood framing for the conduit.  
Refer to the illustration below for location of the hoods’  
electrical box. Refer to the in-line and remote blower  
sections on pages 20–21 and follow installation  
instructions provided with the blower.  
1
FRAMING  
STUDS  
13 /8"  
(333)  
1
8 /4"  
(210) TO  
CENTER  
OF STUD  
IMPORTANT NOTE: Do not run electrical wiring for an  
in-line or remote blower through the ductwork.  
HOOD CENTERLINE  
ELECTRICAL BOX  
Wall framing for low-profile hood.  
FILTER  
GREASE CUP  
SIDE VIEW  
Filter removal.  
Location of electrical box.  
 
Pro Wall Hood Installation  
13  
wolfappliance.com/specs  
Low-Profile Wall Hoods  
HOOD INSTALLATION  
IMPORTANT NOTE: If a backsplash is to be used, it should  
be installed prior to mounting the wall hood. Refer to  
installation instructions provided with the backsplash.  
Install the wall mounting brackets as shown in the illustra-  
tions below. Hang the wall hood on the installation  
brackets in preparation for attaching the hood to wall  
framing.  
Position the hood in the desired location on the wall.  
Depending on the application, install the #10 x 11/2" (38)  
screws with washers or 3" (76) drywall screws through the  
mounting holes on the back plate. Verify that the screws  
engage the wall framing. If not, wall anchors must be  
used.  
If additional support is required for the wall hood, drill  
supplementary mounting holes in the back plate and use  
these holes to attach the hood assembly to the wall  
framing.  
WIDTH OF HOOD  
WIDTH OF HOOD  
1
1
26 /4" (667) TO  
26 /4" (667) TO  
MOUNTING BRACKET  
HOLE CENTERS  
USE ROUND  
AND SLOTTED  
HOLES TO  
SECURE HOOD  
TO WALL  
MOUNTING BRACKET  
HOLE CENTERS  
USE ROUND  
AND SLOTTED  
HOLES TO  
SECURE HOOD  
TO WALL  
1
22 /2" (572)  
CENTERED ON HOOD  
STUDS  
STUDS  
1
1
13 /8"  
(333)  
13 /8"  
(333)  
7
7
1
7 /16" (189)  
7 /16" (189)  
9 /2" (229)  
TO TOP OF  
BRACKET  
TO TOP OF  
BRACKET  
CENTERED  
ON HOOD  
MOUNT  
BRACKETS TO  
WALL FRAMING  
MOUNT  
BRACKETS TO  
WALL FRAMING  
WALL HOLE  
CUT-OUT  
HOOD CENTERLINE  
HOOD CENTERLINE  
Low-profile wall hoods—vertical discharge.  
Low-profile wall hoods—horizontal discharge.  
 
Pro Wall Hood Installation  
14  
24" and 27" Deep Wall Hoods  
WALL PREPARATION  
For ease of installation, the location of the wood mounting  
support and retaining bracket allow for 1/2" (13) clearance  
at the top of the hood. This gap will be taken up during  
final mounting of the hood to the mounting support.  
Construct the wood wall framing flush with the wall studs  
and centered in the location that the hood will be  
mounted. Finish the wall surface.  
Refer to the illustration below for the location of mounting  
holes for pro 24" (610) and 27" (686) deep wall hoods, one  
on each side of the back plate.  
Attach the wood mounting support provided with the  
hood. Refer to the illustration below. The mounting  
support should be centered within the desired location of  
the hood. Use the 3" (76) screws provided to attach the  
mounting support to the wall. The screws should be  
located to correspond with wall framing and countersunk  
so that they are below flush.  
Framing must be tied together and to ceiling joists to  
provide enough structural strength to support the  
weight of the hood and internal blower, if applicable.  
Install the retaining brackets to the wood mounting  
support at the locations shown in the illustration and the  
chart below. Use the #10 X 11/2" (38) screws and washers  
provided to secure the brackets in place. The brackets  
should be mounted 1/2" (13) above the top of the wood  
mounting support.  
Wood Mounting Support  
WIDTH OF HOOD  
30" (762)  
36" (914)  
42" (1067)*  
48" (1219)*  
54" (1372)*  
60" (1524)*  
66" (1676)*  
A
113/4" (298)  
121/4" (311)  
151/4" (387)  
181/4" (464)  
211/4" (540)  
241/4" (616)  
271/4" (692)  
RETAINING  
BRACKET  
1
2
/2"  
1
/2" (13)  
(64)  
MOUNTING  
HOLE  
1
15 /8"  
(384)  
TO BOTTOM  
OF HOOD  
7
4
/16"  
A
(113)  
CENTER  
OF HOOD  
Wood mounting support.  
Location of mounting holes.  
 
Pro Wall Hood Installation  
15  
wolfappliance.com/specs  
24" and 27" Deep Wall Hoods  
HOOD PREPARATION  
Separate the transition from the back plate by  
removing the shipping nut from the inside of the back  
plate.  
IMPORTANT NOTE: For 24" (610) and 27" (686) deep  
wall hoods using an internal blower, refer to installation  
instructions provided with the blower assembly. Install the  
internal blower to the back plate assembly prior to  
mounting the hood.  
Position the back plate in the desired location and  
mark the mounting holes on the wood support. Drill  
pilot holes for the mounting hardware.  
If a duct cover is to be used, follow the instructions on  
page 9 before installing the hood. If you are installing a  
recirculating kit, refer to instructions included with the kit  
before installing the hood.  
If you are installing an in-line or remote blower, drill a  
7/8" (22) hole through the wood framing for the conduit.  
Refer to the illustration below for location of the hoods'  
electrical box. Refer to the in-line and remote blower  
sections on pages 20–21 and follow installation  
instructions provided with the blower.  
The hood is shipped with the back plate and transition  
assembly attached. The transition is shipped upside  
down in the top of the hood. It must be removed and  
reinstalled in the proper position.  
IMPORTANT NOTE: Do not run electrical wiring for an  
in-line or remote blower through the ductwork.  
Remove the filters by pushing each filter up at the  
angle it is placed in, and rotate down. Remove the  
center filter first. Then take out the grease cups placed  
on the bottom edge of the hood coinciding with the  
bottom edge of the filters. Gloves should be worn  
when handling filters.  
Detach the back plate and transition assembly from the  
hood by removing the top and back screws. Do not  
discard the screws, they will be used in the installation.  
Refer to the illustration below.  
ELECTRICAL BOX  
Back plate and transition.  
Location of electrical box.  
 
Pro Wall Hood Installation  
16  
24" and 27" Deep Wall Hoods  
REATTACH BACK PLATE  
HOOD INSTALLATION  
Attach the transition to the back plate using the four  
shipping screws provided in the hardware mounting kit.  
Reinstall the shipping screws removed previously from the  
top and back of the back plate. Seal with duct tape to  
ensure a tight seal from the transition to the back plate.  
IMPORTANT NOTE: If a backsplash is to be used, it should  
be installed prior to mounting the wall hood. Refer to  
installation instructions provided with the backsplash.  
Align the mounting holes in the back plate of the hood  
assembly with the retaining brackets on the wood  
mounting support. Refer to the illustration below for  
location of the mounting holes, one on each side of the  
back plate.  
If additional support is required, drill supplementary  
mounting holes in the back plate and use these holes to  
attach the hood assembly to the wall framing.  
Position the hood and install the #10 x 11/2" (38) screws  
and washers provided through the mounting holes on the  
back plate. Verify that the screws engage the mounting  
support. Attach the transition to existing ductwork with  
sheet metal screws and seal with duct tape. Refer to the  
illustration below.  
1
2
/2"  
(64)  
MOUNTING  
HOLE  
7
4
/16"  
(113)  
Location of mounting holes.  
Hood installation.  
 
Pro Wall Hood Installation  
17  
wolfappliance.com/specs  
All Pro Wall Hoods  
WIRING CONNECTIONS  
FILTER INSTALLATION  
Run a 120 V AC, 15 amp circuit power cable from the  
service panel to the electrical box on the back plate.  
Slide the grease cups along the bottom edge of the hood  
so that the lip of the grease cup overhangs slightly.  
Run the conduit connector through the holes in the  
back plate. Refer to the illustration below for the  
location of the electrical box.  
To install the filters, orient each filter with lines running  
vertically. Position the top edge of the filter as shown in  
the illustration below. While pressing up against the  
spring, rotate the bottom edge of the filter into position  
next to the grease cup. Gloves should be worn when  
handling filters.  
Insert the conduit through the hole on top of the back  
plate to the electrical box.  
Remove the electrical box cover from the back plate.  
Connect black wire to power supply black wire, white  
wire to power supply white wire and green wire to  
green wire or bare wire.  
The illustration below shows a 27" (686) deep wall hood,  
with the filter sloping up from front to back. For low-profile  
and 24" (610) deep hoods, the filter will slope down from  
front to back.  
Place all wiring connections inside the electrical box  
and reinstall on the back plate in the upper right-hand  
corner. Make sure that the wires are secure and that no  
wires are pinched between the cover and box.  
Before servicing, switch power off at the service panel  
and lock the service disconnecting means to prevent  
power from being switched on accidentally. If it cannot  
be locked, securely fasten a prominent warning tag, to  
the service panel.  
FILTER  
GREASE CUP  
SIDE VIEW  
Filter installation.  
ELECTRICAL BOX  
Location of electrical box.  
 
Pro Wall Hood Installation  
Wolf Nameplate  
18  
Blower Assemblies  
The Wolf logo nameplate does not come installed on the  
hood since there are various locations that the nameplate  
can be attached.  
Pro ventilation hoods are shipped without the blower  
assembly. Internal, in-line and remote blowers are avail-  
able through your authorized Wolf dealer. For local dealer  
information, visit the find a showroom section of our  
website, wolfappliance.com.  
Once you've decided on the location for the nameplate,  
clean the mounting area with rubbing alcohol. Remove the  
backing paper from the nameplate. Position the nameplate  
aligned parallel with the bottom edge of the hood and  
press into place.  
The blower will vary in size and is dictated by the cooking  
surface, the volume of air that needs to be moved and the  
length of the duct run. Refer to ventilation recommenda-  
tions in the Wolf design guide.  
IMPORTANT NOTE: Use only a Wolf blower with the pro  
ventilation hood.  
IMPORTANT NOTE: Refer to specific installation instruc-  
tions provided with each blower assembly for additional  
mounting and wiring instructions.  
 
Pro Wall Hood Installation  
Internal Blowers  
19  
wolfappliance.com/specs  
IMPORTANT NOTE: For low-profile wall hoods using the  
500 CFM internal blower, refer to installation instructions  
provided with the blower assembly. Install the internal  
blower prior to mounting the hood.  
BLOWER INSTALLATION—24" AND 27" WALL HOODS  
Assemble the blower housing to the blower mounting  
plate. Follow installation instructions included with the  
blower assembly for proper installation.  
IMPORTANT NOTE: For 24" (610) and 27" (686) deep  
wall hoods using an internal blower, refer to installation  
instructions provided with the blower assembly. Install the  
internal blower to the hood back plate assembly prior to  
mounting the hood.  
Attach the blower assembly to the hood back plate.  
To attach, slide the blower mounting plate over the  
weld studs and secure with eight nuts (provided with  
the blower). Refer to the illustration.  
Verify that the blower discharge aligns with the  
discharge cut-out in the hood back plate.  
IMPORTANT NOTE: Use wire connectors or wire nuts  
approved by UL or C/UL.  
Install the hood and blower assembly to the wall.  
Secure the power cord(s) without damaging or  
pinching while installing the hood.  
Follow hood installation instructions on pages 12–13  
for low-profile wall hoods, and pages 14–16 for 24"  
(610) and 27" (686) deep wall hoods.  
Once the hood installation is complete, plug the blower  
power cord(s) into receptacle(s) located near the center  
of the hood shell. Refer to the illustration below. Use  
the clips on the interior of the hood to secure excess  
power cord.  
HOOD  
BACK  
PLATE  
IMPORTANT NOTE: Before turning the power on to the  
BLOWER  
MOUNTING  
PLATE  
ventilation hood, make sure the blower is off.  
BLOWER  
HOUSING  
Internal blower assembly.  
BLOWER  
RECEPTACLE(S)  
Location of receptacle(s).  
 
Pro Wall Hood Installation  
In-Line and Remote Blowers  
20  
Locate the blower so that the length of the duct run and  
number of elbows and transitions are kept to a minimum.  
The duct run should be no longer than 50' (15 m). If  
possible, remote blowers should be located between wall  
studs or roof rafters. Avoid pipes, wires and other  
Refer to the illustrations below for overall dimensions of  
Wolf in-line and remote blowers. Installation instructions  
shipped with each Wolf ventilation product provide  
detailed specifications. These instructions can also be  
found on our website, wolfappliance.com/specs.  
ductwork. Be sure there is enough space for transitions  
needed between the blower and connecting ductwork. For  
best performance, locate transitions nearest the blower.  
IN-LINE AND REMOTE BLOWER DIMENSIONS  
7
24 /8"  
(632)  
3
24 /8"  
(619)  
3
18"  
11 /4"  
(298)  
12"  
(457)  
(305)  
1
18 /2"  
(470)  
1
4 /2"  
(114)  
8"  
(203)  
1
21 /2"  
22"  
18"  
1
(546)  
(559)  
12 /4"  
(311)  
(457)  
600 CFM in-line blower.  
1100 CFM in-line blower.  
18" (457)  
21" (533)  
10"  
10"  
3
20 /4"  
(527)  
(254)  
1
(254)  
29 /2"  
1
29 /2"  
1
28 /4"  
(749)  
(749)  
(718)  
10" (254)  
Diameter  
10" (254)  
Diameter  
10" (254)  
Diameter  
3
3
14 /4"  
(375)  
1
1
14 /4"  
(375)  
15 /2"  
(394)  
29 /2"  
1
29 /2"  
1
(749)  
24 /2"  
(749)  
(622)  
1
3
10 /8"  
10 /8"  
14"  
(257)  
(264)  
(356)  
3
4
/4"  
1
7
1
7
22"  
3
(121)  
/4"  
25"  
/4"  
24 /4"  
(629)  
(559)  
(184)  
(635)  
(184)  
600 CFM and 900 CFM remote blower.  
1200 CFM remote blower.  
1500 CFM remote blower.  
 
Pro Wall Hood Installation  
21  
wolfappliance.com/specs  
In-Line and Remote Blowers  
BLOWER INSTALLATION  
Plug the cord assembly into the receptacle located  
near the center of the hood shell. Refer to the illustra-  
tion below. Use the clips on the interior of the hood to  
secure excess power cord.  
IMPORTANT NOTE: Refer to specific installation instruc-  
tions provided with each blower assembly for additional  
mounting and wiring instructions.  
Reinstall the electrical box cover and screws in the  
upper right-hand corner of the hood. Make sure all  
wires are secure and that no wires are pinched  
between the cover and box.  
IMPORTANT NOTE: Use wire connectors or wire nuts  
approved by UL or C/UL.  
Follow specific wiring instructions provided with each  
blower. Black (L1) to black, white (neutral) to white, or  
white to blue, or white to brown (depending on model)  
and green to grounding screw. Run ROMEX cable to  
the hood.  
IMPORTANT NOTE: Before turning the power on to the  
ventilation hood, make sure the blower is off.  
Insert 6" (152) of ROMEX cable through the knockout  
opening and into the electrical box on the back plate of  
the hood. Secure the cable to the electrical box with an  
appropriate connector.  
When making electrical connections, make sure the  
electrical power is turned off at the power source or  
circuit breaker before proceeding.  
Locate the cord assembly provided with the blower.  
The cord assembly has two leads, black (L1) and white  
(neutral). Connect these leads to the leads from the  
blower, black to black and white to white.  
Connect all green and bare wires together to the  
ground screw in the electrical box.  
BLOWER  
RECEPTACLE(S)  
Location of receptacle(s).  
 
Service Information  
Troubleshooting  
22  
Service Information  
IMPORTANT NOTE: If the pro ventilation hood does not  
If service is necessary, maintain the quality built into your  
ventilation hood by calling a Wolf authorized service  
center.  
operate properly, follow these troubleshooting steps:  
Verify that electrical power is being supplied to the  
ventilation hood.  
To obtain the name and number of a Wolf authorized  
service center, check the contact & support section of our  
website, wolfappliance.com or call Wolf customer service  
at 800-332-9513.  
Check electrical connections to ensure that the  
installation has been completed correctly.  
Refer to the troubleshooting guide in the Wolf  
pro ventilation hoods use & care guide.  
When calling for service, you will need the model and  
serial numbers of the ventilation hood. This information is  
found on the product rating plate, located inside the left  
wall of the hood shell. Refer to the illustration below.  
If the ventilation hood still does not operate properly,  
contact a Wolf authorized service center. Do not  
attempt to repair the ventilation hood yourself. Wolf is  
not responsible for service required to correct a faulty  
installation.  
RATING PLATE (INSIDE HOOD)  
Location of rating plate.  
 
The information and images in this guide are the copyright property of Wolf Appliance, Inc. Neither this guide nor any information or images contained  
herein may be copied or used in whole or in part without the express written permission of Wolf Appliance, Inc. ©Wolf Appliance, Inc. all rights reserved.  
 
WOLF APPLIANCE, INC. P. O. BOX 44848 MADISON, WI 53744 WOLFAPPLIANCE.COM 800.332.9513  
811504 REV-B  
4/2010  
 

Weed Eater Trimmer 545117527 User Manual
Westinghouse eBook Reader SB926SL User Manual
Whirlpool Range 8522773A User Manual
Winegard Satellite TV System WB 2700 User Manual
Wolf Appliance Company Ventilation Hood PW482418 User Manual
Xantech Stereo Amplifier PA435X User Manual
Yamaha Electronic Keyboard 205M User Manual
Yamaha Music Mixer AM802 User Manual
Zanussi Oven 237005 User Manual
Zanussi Refrigerator 113156 User Manual